A Study on the use of Lithium Chloride solution and Calcium Chloride solution to Dehumidify in Air-Conditioned Rooms to Reduce Energy Consumption in Air Conditioners
Keywords:
air-condition, dehumidifier, energy save, liquid desiccantAbstract
This research investigated the use of lithium chloride (LiCl) and calcium chloride (CaCl2) solutions as liquid desiccants for moisture absorption from air. The desiccant solution was stored in a reservoir located at the base of the liquid desiccant dehumidifier unit and circulated by a dedicated pump. The entire system was installed inside a test room measuring 2 m × 2 m × 2 m to reduce the latent heat load of a small-scale split-type air conditioning system. The experimental chamber was constructed with 0.2 m thick Expanded Polystyrene: EPS insulated walls. The test conditions were established as follows: indoor air temperatures were set at 30°C 35°C and 40°C, with corresponding relative humidity levels of 70% 80% and 90%. The results showed that the electrical energy consumption of the air conditioner without a desiccant system ranged from 0.182–0.192 kWh at 30°C 0.208–0.255 kWh at 35°C and 0.259–0.337 kWh at 40°C. When LiCl solution was used as the moisture absorbent, the electrical energy consumption of the air conditioner decreased by 0.020–0.020 kWh at 30°C, 0.011–0.042 kWh at 35°C, and 0.040–0.082 kWh at 40°C. Similarly, when CaCl2 solution was applied, the energy consumption was reduced by 0.036–0.043 kWh at 30°C –0.005–0.036 kWh at 35°C, and 0.019–0.064 kWh at 40°C. The maximum reduction in electricity consumption achieved by the LiCl solution was 24%, while the CaCl2 solution achieved a maximum reduction of 23.62%. In terms of comparative performance, CaCl2 showed better energy-saving potential at 30°C, both solutions performed comparably at 35°C, and LiCl demonstrated superior performance at 40°C.
References
Attia, A., A. Teamah, M., M. El-Maghlany, W., & El-Saharty, A. E. (2018). Theory and applications.In Z. Saghir (Ed.), ICTEA: International Conference on Thermal Engineering (pp. 1–4). Toronto Metropolitan University.
Bouzenada, S., Kaabi, A. N., Frainkin, L., Salmon, T., & Léonard, A. (2016). Experimental comparative study on lithium chloride and calcium chloride desiccants. Procedia Computer Science, 83, 718–725. https://doi.org/10.1016/j.procs.2016.04.162
Çengel, Y. A., & Ghajar, A. J. (2015). Heat and mass transfer: Fundamentals & applications. McGraw-Hill Education.
Chen, X., Riffat, S., Bai, H., Zheng, X., & Reay, D. (2020). Recent progress in liquid desiccant dehumidification and air-conditioning: A review, Energy and Built Environment, 1(1), 106–130. https://doi.org/10.1016/j.enbenv.2019.09.001
Conde, M. R. (2004). Properties of aqueous solutions of lithium and calcium chlorides: formulations for use in air conditioning equipment design. International Journal of Thermal Sciences, 43(4), 367–382. https://doi.org/10.1016/j.ijthermalsci.2003.09.003
FlyCarpet Inc. (2024). About Psychrometric Chart + Duct Calculator. https://www.flycarpet.net/en/psychart
Electricity Generating Authority of Thailand [EGAT]. (2025). Annual report 2024 [In Thai]. https://www.egat.co.th/home/wp-content/uploads/2025/04/EGAT-AR_TH_2024_250411.pdf
Kumar, K., Singh, A., Shaik, S., Saleel, C. A., Aabid, A., & Baig. M. (2022). Comparative analysis on dehumidification performance of KCOOH–LiCl Hybrid Liquid desiccant air-conditioning system: An Energy-Saving Approach. Sustainability, 14(6), 3441. https://doi.org/10.3390/su14063441
Nachaisin, W., Niyomsin, S., Kerdlap, P., & Pongpakpian, S. (2023). Design of a rotary dehumidifier [In Thai]. EAU Heritage Journal Science and Technology, 17(2), 234–243. https://he01.tci-thaijo.org/index.php/EAUHJSci/article/view/262217
Meteorological Department. (2024). Thailand weather [In Thai]. https://www.tmd.go.th/info/ภูมิอากาศของประเทศไทย-หน้า-2
Parakul, S., & Jaitrong, K. (2025). The development of a temperature and humidity control system in a split-type ceiling-suspended air conditioner to optimize energy usage in classrooms at Siam Technology College [In Thai]. Journal of Energy and Environment Technology of Graduate School Siam Technology College, 12(1), 72–80. https://ph01.tci-thaijo.org/index.php/JEET/article/view/262052
Shivaprasad, K. V., Roy, S., Giampieri, A., Smallbone, A., & Roskilly, A. P. (2025). Experimental and numerical investigation to optimise liquid desiccant system for advanced air conditioning. Scientific Reports, 15(1), 7151. https://doi.org/10.1038/s41598-025-88738-2
Swangphol, N., Bunyarittikit, S., Thipyophas, C., & Khwansuwan, P. (2024). Suitable tools for thermal comfort evaluationin air-conditioned exercise facilities [In Thai]. Sarasatr: Journal of Architecture and Design, 7(3), 622–635. https://so05.tci-thaijo.org/index.php/sarasatr/article/view/272300/183879.
The National Statistical Office [NSO]. (2025). NSO data catalog [In Thai]. https://catalog.nso.go.th/dataset?groups=os-13